Stock code:002309
Wechat Num:
SZ002309

Aluminum alloy wire

Author: Time:2015-09-11 Hit:3129

1. The product standard
IEC 61089-61089
2. The scope of application and main characteristics
Can replace part of aluminium wire or steel core aluminum stranded wire is used for overhead transmission lines; Continuous use temperature can reach 90 ℃, the use of heat-resisting aluminum alloy conductor temperature can reach 150 ℃ and above, current-carrying capacity is good, and good anticorrosive property.
3. A typical product structure

5. Computing section (was)

Marine communication cable

Structure (n/mm).

Computing section (was)

The diameter of wire Dia (mm)

Quality of unit length (kg/km)

Calculation of tensile force (kN)

Dc resistance of 20 ℃ (Ω/km)

The root number no.

The diameter of the dia.

16

7

1.83

18.4

5.49

50.4

5.43

1.7896

25

7

2.29

28.8

6.86

78.7

8.49

1.1453

40

7

2.89

46.0

8.68

125.9

13.58

0.7158

63

7

3.63

72.5

10.9

198.3

21.39

0.4545

100

19

2.78

115

13.9

316.3

33.95

0.2877

125

19

3.10

144

15.5

395.4

42.44

0.2302

160

19

3.51

184

17.6

506.1

54.32

0.1798

200

19

3.93

230

19.6

632.7

67.91

0.1439

250

19

4.93

288

22.0

790.8

84.88

0.1151

315

37

3.53

363

24.7

998.9

106.95

0.0916

400

37

3.98

460

27.9

1268.4

135.81

0.0721

450

37

4.22

518

29.6

1426.9

152.79

0.0641

500

37

4.45

575

31.2

1585.5

169.76

0.0516

560

61

3.67

645

33.0

1778.4

190.14

0.0516

630

61

3.89

725

35.0

2000.7

213.90

0.0458

710

61

4.13

817

37.2

2254.8

241.07

0.0407

800

61

4.38

921

39.5

2540.6

271.62

0.0361

900

91

3.81

1036

41.8

2861.1

305.58

0.0321

1000

91

4.01

1151

44.1

3179.0

339.53

0.0289

1120

91

4.25

1289

46.7

3560.5

380.27

0.0258

1250

91

4.49

1439

49.4

3973.7

424.41

0.0231