I. Product Name

Medium Voltage Power Cable

II. Main Properties

  • Voltage Class: 35 kV and below
  • Operating Temperature Range: -15 °C ~ 90 °C (XLPE Insulated)
  • Minimum Installation Temperature: 0 °C
  • Storage Temperature Range: -15 °C ~ 50 °C

  • Minimum Bending Radius:

    project

    single conductor cable

    bank cable

    unarmored

    Armored

    unarmored

    Armored

    Minimum cable bending radius during installation

    20D

    15D

    15D

    12D

    Note: D is the outer diameter of the cable

    III. Product Application

    This product is applicable to power systems with rated voltage up to and including 35 kV (Um=40.5 kV) in distribution networks or industrial installations, for power transmission and distribution on power transmission and distribution lines.
    The cable can be laid indoors, in tunnels, cable trenches and pipelines, or buried in loose soil. It can withstand a certain laying tension.
    It is most commonly used in urban underground power grids, outgoing lines of power stations, internal power supply of industrial and mining enterprises, etc.

    IV. Reference Standards

    GB/T 12706.2-2020
    GB/T 12706.3-2020

    V. Product Types

    Copper Conductor:
    YJV, YJY, YJV22, YJY22, YJV23, YJY23,
    YJV62, YJY62, YJV63, YJY63, YJV32, YJY32,
    YJV33, YJY33, YJV72, YJY72, YJV73, YJY73
    Z(A/B/C/D)-YJV, YJY, YJV22, YJY22, YJV23, YJY23,
    YJV62, YJY62, YJV63, YJY63, YJV32, YJY32,
    YJV33, YJY33, YJV72, YJY72, YJV73, YJY73
    WDZ(A/B/C/D)-YJY, YJV23, YJY23, YJV63, YJY63,
    YJV33, YJY33, YJV73, YJY73
    Aluminum Conductor:
    YJLV, YJLY, YJLV22, YJLY22, YJLV23, YJLY23,
    YJLV62, YJLY62, YJLV63, YJLY63, YJLV32, YJLY32,
    YJLV33, YJLY33, YJLV72, YJLY72, YJLV73, YJLY73
    Z(A/B/C/D)-YJLV, YJLY, YJLV22, YJLY22, YJLV23, YJLY23,
    YJLV62, YJLY62, YJLV63, YJLY63, YJLV32, YJLY32,
    YJLV33, YJLY33, YJLV72, YJLY72, YJLV73, YJLY73
    WDZ(A/B/C/D)-YJLY, YJLV23, YJLY23, YJLV63, YJLY63,
    YJLV33, YJLY33, YJLV73, YJLY73

    VI. Product Specifications

    Number of Cores:
    1 core, 3 cores
    Cross-sectional Area:
    25 mm², 35 mm², 50 mm², 70 mm², 95 mm², 120 mm²,
    150 mm², 185 mm², 240 mm², 300 mm², 400 mm², 500 mm²,
    630 mm², 800 mm², 1000 mm²