Power transmission of fix installation of 50HZ and rated voltage of 3.6/6kV-26/35kV.
GB/T 12706.2-2008 <Rated voltage 1kV (Um=1.2kV) to 35kV (Um=40.5kV) extruded insulated power cables and accessories. Part 2: rated voltage 6KV (Um=7.2kV) to 30KV (Um=36kV) cables. >
GB/T 12706.3-2008 <Rated voltage 1kV (Um=1.2kV) to 35kV (Um=40.5kV) extruded insulated power cables and accessories. Part 3: rated voltage 35KV (Um=40.5kV) cables. >
Rated voltage is 3.6/6kV~26/35kV.
Max long-term working temperature for cable conductor is 90℃.When in short circuit (max 5s), max temperature of cable conductor not exceeding 250℃.
Ambient installation temperature should not be less than 0℃, the Min. Bending radium should be no less than: single core cables minimum bend diameter not less than 20D (mm); multiple core cables minimum bend diameternot less than 15D (mm).