Applied for fixed-installation, alternative current 50Hz,rated voltage 0.6/1kv and below for power supply in the transmitting lines.Executive standard:GB12706-2008 rated voltage 1kV(Um=1.2kV) and 3kV(Um=3.6kV).
1)PVC insulated power cables
1. Max rated temperature for cable conductor: 70℃.
2. When in short circuit (max 5s), max temperature of cable conductor not exceeding 160℃.
33. Cable installed temperature not below 0℃.Min bending radius: Single core cables: 20D (mm) Multiple core cables: 15D (mm)
D represents actual outer diameter.
2)XLPE insulated power cables
1. Max rated temperature for cable conductor: 90℃.
2. When in short circuit (max 5s), max temperature of cable conductor not exceeding 250℃, overload temperature not exceeding 130℃.
3. Cable installed temperature not below 0℃. Min bending radius :Single core cables: 20D (mm) Multiple core cables: 15D (mm)
D represents actual outer diameter.
Type | Name | ||
Copper | Al | ||
VV | VLV | PVC insulated and sheathed power cables | |
VY | VLV | PVC insulated and PE sheathed power cables | |
VV22 | VLV22 | PVC insulated, steel tape armored and PVC sheathed power cables | |
VV23 | VLV23 | PVC insulated, steel tape armored and PE sheathed power cables | |
VV32 | VLV32 | PVC insulated, thin round steel armored and PE sheathed power cables | |
VV33 | VLV33 | PVC insulated, thin round steel armored and PE | |
YJV | YJLV | XLPE insulated and PVC sheathed power cables | |
YJY | YJLY | XLPE insulated and PE sheathed power cables | |
YJV22 | YJLV22 | XLPE insulated, steel tape armored and PE sheathed power cables | |
YJV23 | YJLV23 | XLPE insulated, steel tape armored and PE sheathed power cables | |
YJV32 | YJLV32 | XLPE insulated, thin round steel wire armored and PVC sheathed power cables | |
YJV33 | YJLV33 | XLPE insulated, thin round steel wire armored and PE sheathed power cables |